search-loading

Active Chilled Beams


Application of Induction Diffusers

TROX induction diffusers are used in air-water systems to provide ventilation, heating and cooling of room air.

Type DID301 & DID302 Series Active Chilled Beam

DID300_US_170
  • Flush ceiling active chilled beam
  • Nominal width: 12" to suit t-bars at 1 ft centers
  • High cooling capacity with low conditioned fresh air flow rates
  • Heat exchangers for two or four pipe systems
  • Two induced air grille design options
  • One-way (DID301-US) and two-way (DID302-US) models available
  • One-way or two-way vertically mounted heat exchangers with condensate drip trays for low chilled water flow temperatures
  • Heating and/or cooling is possible
  • Selection software featuring detailed comfort data and terminal velocities

more details

Manufactured in the USA

rectangular

primary air:
Up to 25 cfm/lf

L: 4 ft, 6ft, 8ft and 10ft (other sizes available upon request)
H: 9 1/2 in

Cooling capacity up to 9600 Btu/h
Heating capacity up to 11 mbh

Extruded aluminum face

Type DID604 Active Chilled Beam

DID_604_US_170
  • Flush ceiling active chilled beam
  • Nominal width: 24" to suit t-bars at 2 ft centers
  • Four-way throw air pattern
  • Two or four pipe heat exchanger coils (cooling / heating and cooling)
  • Adjustable air control blades
  • Adjustable induction nozzle sizes
  • Primary air ducted to upper air chamber via a side or top inlet
  • Selection software featuring detailed comfort data and terminal velocities





more details

Manufactured in the USA

square, rectangular

primary air:
Up to 100 cfm

L: 2ft and 4ft
H: 8 1/2 in

Cooling capacity up to 5500 Btu/h
Heating capacity up to 6 mbh

Aluminum & steel diffuser face

Type DID632 Active Chilled Beam

DID_632_US_170
  • Flush ceiling active chilled beam
  • Nominal width: 24" to suit t-bars at 2 ft centers
  • High cooling performance with low primary air flow air requirements
  • Two face designs
  • Two or four pipe configuration (heating and/or cooling)
  • Adjustable air control blades
  • Selection software featuring detailed comfort data and terminal velocities
  • Standard and HC versions available





more details

Manufactured in the USA

rectangular

primary air:
Up to 300 cfm

L: 4ft - 10ft
H: <9in

Cooling capacity up to 15000 btu/h
Heating capacity up to 12 mbh

Aluminum & steel diffuser face

Type DID-E

  • Flush ceiling active chilled beam
  • One-way air discharge
  • Ideal for individual rooms in hotels or hospitals
  • Induction and supply air grilles in various designs
  • Side entry spigot for fresh air
  • Heat exchanger horizontal without condensate drip tray
  • Low height construction

more details

rectangular

primary air:
Up to 165 cfm

L: 22in and 24in
W: 3.4ft and 5ft
H: 8in

Cooling capacity up to 7,500 btu/h
Heating capacity up to 2.0 mbh

Type QLCI Displacement with Induction

QLCI_170
  • Specifically designed for classroom and healthcare applications
  • Nominal width: 13.5"
  • Top or end-mounted primary air inlet
  • Vertically mounted heat transfer coil with condensate tray allows operation with operable windows
  • Selection software featuring detailed comfort data and terminal velocities




more details

Manufactured in the USA

rectangular

primary air:
Up to 180 cfm

L: 68 in or 88 in
H: 30 in

Cooling capacity up to 6800 btu/h
Heating capacity up to 4.5 mbh

Basic cabinets constructed of 16 gauge steel

Type DID312

DID312_170
  • Flush ceiling active chilled beam
  • Nominal width 300 mm
  • Four options of induced air grille design
  • Heat exchanger vertically mounted with condensate drip tray for low chilled water temperatures
  • Side entry spigot for fresh air
  • Supply-extract-air combination available

more details

rectangular

primary air:
5 – 70 l/s
18 – 252 m³/h

L: 900 – 3000 mm
H: 210 and 241 mm

Cooling capacity up to 1800 W
Heating capacity up to 1250 W

Type DID600B

  • Flush ceiling mounting active chilled beam
  • Nominal width 600 mm
  • Top or side entry spigot for fresh air
  • Heat exchanger horizontal
  • Supply-extract-air combination available

more details

rectangular

primary air:
3 – 53 l/s
10 – 190 m³/h

L: 900 – 3000 mm
W: 600 mm
H: 210 mm

Cooling capacity up to 1700 W
Heating capacity up to 1800 W

Type DID-R

  • Circular flush ceiling active chilled beam
  • Many design configurations available
  • Circular or square face
  • Side entry spigot for fresh air
  • Heat exchanger vertically mounted with condensate drip tray for low chilled water temperatures
  • Installation into false ceilings

more details

circular, square

primary air:
12 – 25 l/s
43 – 252 m³/h

Ø 598 mm
 593, 598, 618 und 623 mm
H: 250 mm

Cooling capacity up to 500 W
Heating capacity up to 1200 W

Type IDH

IDH
  • For installation in large height spaces
  • One or two-way air discharge
  • Adjustable discharge
  • High capacity for large halls
  • Top entry spigot for fresh air
  • Heat exchanger vertically mounted with condensate drip tray for low chilled water temperatures
  • Freely suspended installation

more details

rectangular

primary air:
up to 1670 l/s
up to 6000 m³/h

L: 1500, 2000 and 2500 mm
W: 305 and 548 mm
H: 1405 mm

Cooling capacity up to 27 kW
Heating capacity up to 10 kW

Type DID600B-L

  • Multi-service active chilled beam
  • Flush-mounted in the ceiling
  • Integrated linear light fittings
  • Low height construction
  • Top or side entry spigot for fresh air
  • Heat exchanger horizontal
  • Project bespoke dimensions

more details

rectangular

primary air:
3 – 43 l/s
11 – 155 m³/h

L: 1500 – 3000 mm
W: 593 mm
H: 210 mm

Cooling capacity up to 1610 W
Heating capacity up to 1730 W

Type DID601 & DID602 Series Active Chilled Beams

DID602_US_170
  • Flush ceiling mounted active chilled beam
  • Nominal width: 24" to suit t-bars at 2 ft centers
  • Top or end-entry spigot
  • High cooling performance with low primary air flow air requirements
  • Perforated face design
  • Two or four pipe configuration (cooling / heating and cooling)
  • Three nozzle sizes
  • Available with built in extract air grille
  • Selection software featuring detailed comfort data and terminal velocities
  • Standard and HC versions available





more details

Manufactured in the UK

rectangular

primary air:
Up to 20 cfm/lf

L: 4ft - 10ft
H: <10in

Cooling capacity up to 12000 Btu/h
Heating capacity up to 12 mbh

Extruded aluminum face

Reference

Tahoe Center for Environmental Sciences

TROX active chilled beams type DID602 installed in laboratories and classrooms
Reference

Contact

trox_usa_exterior_company_page_76

TROX USA, Inc.

4305 Settingdown Circle
Cumming
Georgia 30028
Tel: +1-770-569-14 33

Contact and locations