- 4 Digital inputs for potential-free switch contacts
- 2 Digital outputs (changeover relay)
- 2 Analogue inputs for 0-10 V signals
- 1 Analogue output with 0-10 V signal
- Supply voltage 24 V AC/DC, with double terminals for easy installation
- LON bus connection via FTT10A transceiver, with double terminals for easy installation
- Type of protection for housing: IP 65
Summation/balancing function
- Available input signals:
- 2 Volume flow signals via analogue 0-10 V inputs
- 16 Volume flows via standard network variables on LON bus
- 4 Switchable constant volume flows (exhaust hoods, cabinets, etc.) via potential-free switches at the digital inputs - Output signal (calculated volume flow sum/balance) can be picked up via:
- Analogue output as a 0-10 V signal
- Standard network variable via LON bus
Generation of group alarm messages
- Available inputs:
- 16 Alarm inputs via standard network variables on LON bus - Group alarm output can be picked up via:
- Digital output with changeover relay for switch contacts
- Standard network variable via LON bus